Technical Parameters

Main  
RangeUEW6、UEW6DHG
Product or Component TypeUndervoltage Trip Device
Device NameQTW45
Voltage Release TypeUndervoltage trip
Device ApplicationControl
Control Type Standard
Mounting TypeDraw-out type, fixed type
Range Compatibility UEW6-2000、 UEW6-3200、UEW6-4000、UEW6DHG-2500
Complementary 
Rated VoltageAC400V  AC230V  DC220V  AC110V   DC110V     AC24V    DC24V     
Instantaneous Current1.3A       2.1A      2.1A      2.1A     2.5A      8.6A      10A     
Steady Current21mA     21mA    21mA     90mA     90mA   235mA    250mA       
Operating Voltage(0.35...0.7)Ue
Reliable Closing Voltage(0.85...1.1)Ue
Reliable Non-Closing Voltage≤0.35 Ue
Time of DelayInstantaneous、1s、3s、5s