| Main | |
| Product Series | HFUC5 |
| Product or Component Type | Contactor |
| Device short name | HFUC5-25 |
| Contactor application | Motor control Resistive load |
| Utilisation category | AC-3 AC-4 AC-1 |
| Poles description | 3P |
| [Ue] Rated operational voltage | Power circuit: ≤ 690 V AC 50/60Hz |
| [Ie] Rated operational current | 25 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit 40 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
[Us] Control circuit voltage (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Code: B7 CC7 D7 E7 F7 FE7 FC7 M7 P7 U7 Q7 V7 N7 | |
| Complementary | |
| Motor power kW | 5.5 kW at 220/230 V AC 50/60 Hz (AC-3) 11 kW at 380/400 V AC 50/60 Hz (AC-3) 15 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Motor power hp | 2 hp at 110…120 V AC 50/60 Hz for 1 phase motors 3 hp at 200…208 V AC 50/60 Hz for 1 phase motors 3 hp at 220…240 V AC 50/60 Hz for 1 phase motors 7.5 hp at 200…208 V AC 50/60 Hz for 3 phases motors 7.5 hp at 220…240 V AC 50/60 Hz for 3 phases motors 15 hp at 440…480 V AC 50/60 Hz for 3 phases motors 20 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Pole contact composition | 3 NO |
| [Ith] Conventional free air thermal current | 40 A (at ≤60 °C) for power circuit 10 A (at ≤60 °C) for signalling circuit |
| [Icw] Rated short-time withstand current | 240 A ≤40 °C - 10 s for power circuit 380 A ≤40 °C - 1 s for power circuit 50 A ≤40 °C - 10 min for power circuit 120 A ≤40 °C - 1 min for power circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 40 A gG at ≤ 690 V coordination type 2 for power circuit |
| Average impedance | 2 mΩ - Ith 50 Hz for power circuit |
| [Ui] Rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V UL Certified Signalling circuit: 690 V conforming to IEC 60947-5-1 Signalling circuit: 600 V UL Certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] Rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Mechanical durability | 10 M cycles |
| Electrical durability | 1.0 M cycles 25 A AC-3 at Ue ≤ 400 V |
| Control circuit type | AC at 50/60 Hz standard |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.8...1.1 Us (-40…+60 °C): operational AC 50 Hz 0.85...1.1 Us (-40…+60 °C): operational AC 60 Hz 1...1.1 Us (+60…+70 °C): operational AC 50/60 Hz 0.2...0.75 Us (-40…+70 °C): drop-out AC 50/60 Hz |
| Inrush power in VA | 63 VA 50/60 Hz (at 25 °C) |
| Hold-in power consumption in VA | 9.5 VA 50/60 Hz (at 25 °C) |
| Operating time | Power circuit: 12...22 ms closing, 4...19 ms opening Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Maximum operating rate | Electrical: 600 cycs/h Mechanical: 3600 cycs/h |
| Connections - terminals | Power circuit: screw clamp terminals 1 2.5…10 mm² (AWG 14…8)- cable stiffness: flexible without cable end Power circuit: screw clamp terminals 2 2.5…10 mm² (AWG 14…8) - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 1 1.5…10 mm² (AWG 16…8) - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1.5…6 mm² (AWG 16…10) - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1.5…10 mm² (AWG 16…8) - cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 2.5…10 mm² (AWG 14…8) - cable stiffness: solid without cable end Control circuit: screw clamp terminals 1 1…4 mm² (AWG 18…12) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² (AWG 18…12) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² (AWG 18…12) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² (AWG 18…14) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² (AWG 18…12) - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² (AWG 18…12)- cable stiffness: solid without cable end |
| Tightening torque | Power circuit: 22 lb.in(2.5 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm Power circuit: 22 lb.in(2.5 N·m)- on screw clamp terminals - with screwdriver Philips No 2 Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| Auxiliary contact composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Minimum switching capacity | 24 V,0.1A for C type signalling circuit 17V,5mA for CS type signalling circuit |
| Insulation resistance | > 10 MΩ for signalling circuit |
| Mounting support | Screw 35mm DIN Rail |
| Environment | |
| Standards | GB / T 14048.4, GB/T 14048.5,IEC 60947-4-1, IEC 60947-5-1 UL 60947-4-1, UL 60947-5-1,CSA C22.2 No. 60947-4-1, CSA C22.2 No. 60947-5-1 EN 60947-4-1 (VDE 0660 Teil 102), EN 60947-5-1 (VDE 0660 Teil 200) BS EN 60947-4-1, BS EN 60947-5-1 |
| Product certifications | CCC,UL(cULus Listed) ,VDE,CE,UKCA |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
Permissible ambient air temperature around the device | -40…+60 °C for normal operating +60…+70 °C with derating (for operation in the range of Us...1.1Us) Storage: -60…+80 °C |
| Operating altitude | 0...3000 m without derating |
| Fire resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 92.5 mm |
| Width | 45 mm |
| Depth | 100 mm |
| Net Weight | 0.47 kg |
| Packing Units | |
| Unit type of package 1 | 1 box |
| Number of Units in Package 1 | 1 pcs |
| Package 1 height | 11.1 cm |
| Package 1 width | 5.0 cm |
| Package 1 length | 9.9 cm |
| Package 1 weight | 0.50 kg |
| Unit type of package 2 | 1 carton |
| Number of Units in Package 2 | 30 pcs |
| Package 2 height | 26.4 cm |
| Package 2 width | 29.0 cm |
| Package 2 length | 33.7 cm |
| Package 2 weight | 15.30 kg |
| Offer Sustainability | |
| REACH Regulation | Conforming |
| EU RoHS directive | Conforming |
| Mercury free | Yes |
| China RoHS Regulation | Conforming |
| RoHS exemption information | Yes |
| Contractual warranty | |
| Warranty | 18 months |
Dimensions
HFUC5-25~38 (3P, AC coil)
AC contactor:

Interlock contactor:

Note: The unit is mm. The tolerance for mounting holes: ± 0.5; for other external dimensions: ± 1.5, unless otherwise specified.