Main | |||||||
Product Series | XMC0 | ||||||
Product or Component Type | Definite Purpose Contactors | ||||||
Device Short Name | XMC0-323 | ||||||
Contactor Application | HVAC, refrigeration, heating, data processing, welding, elevators, hoist & cranes, pool, commercial spa, and food service equipment industries, etc. | ||||||
Poles Description | 3P | ||||||
Rated Operational Voltage [Ue] | Power circuit: ≤ 600 V AC 50/60Hz | ||||||
Full Load Ampere [FLA] | 32 A | ||||||
Locked Rotor Ampere [LRA] | 180 A @ 240/277 V AC;150 A @ 480 V AC;120 A @ 600 V AC | ||||||
Resistive Ampere [RES] | 40 A | ||||||
Control Circuit Voltage [Us]
| Code | Voltage | |||||
E | 24 V AC 50/60Hz | ||||||
F | 110-120 V AC 50/60Hz | ||||||
I | 208-220 V AC 50Hz 208-240 V AC 60Hz | ||||||
L | 277 V AC 60Hz | ||||||
N | 380-415 V AC 50Hz 440-480 V AC 60Hz | ||||||
Main Contact Terminals |
| ||||||
Coil Terminals | ![]() | ||||||
Complementary | |||||||
Maximum Horse Power Rating | 5 hp 240/277 V AC, 1phase 10 hp 240/277 V AC, 3phase 15 hp 480 V AC, 3phase 20 hp 600 V AC, 3phase | ||||||
Pole Contact Composition | 3 NO | ||||||
Pollution Degree | 3 | ||||||
Control Circuit Voltage Limits @ 25℃ (Cold state) | 0.8...1.1 Us: operational AC 50/60 Hz 0.2...0.75 Us: drop-out AC 50/60 Hz | ||||||
Nominal Inrushed VA @ 25℃ (Cold state) | E:55 VA @ 24V 50 Hz, 50 VA @ 24V 60Hz F:65 VA @ 120V 50 Hz, 60 VA @ 120V 60Hz I:45 VA @ 220V 50 Hz, 50 VA @ 240V 60Hz L:50 VA @ 277V 60Hz N:45 VA @ 415V 50 Hz, 60 VA @ 480V 60Hz | ||||||
Nominal Sealed VA @ 25℃ (Cold state) | E:10 VA @ 24V 50 Hz, 8 VA @ 24V 60Hz F:13.5 VA @ 120V 50 Hz, 10 VA @ 120V 60Hz I:9.5 VA @ 220V 50 Hz, 9.5 VA @ 240V 60Hz L:10.5 VA @ 277V 60Hz N:12 VA @ 415V 50 Hz, 13 VA @ 480V 60Hz | ||||||
Maximum Operating Rate | Electrical: 360 cycs/h Mechanical: 3600 cycs/h | ||||||
Tightening Torque | Power circuit: 25 lb-in - on screw terminals Power circuit: 25 lb-in - on box lug terminals Control circuit: 8 lb-in | ||||||
Auxiliary Contact Composition | W/o built-in auxiliary contacts. Additional auxiliary contact modules can be installed if needed. | ||||||
Mounting Support | Screw | ||||||
A2L application: | Suffix w/ “W” : Flame Arrest-protected Components for Use in Refrigeration and Air-conditioning Equipment Employing A2L Refrigerants. | ||||||
Minimum Switching Load | 110 VAC, 1A | ||||||
Environment | |||||||
Standards | UL 60947-4-1, GB/T 14048.4, IEC 60947-4-1, EN 60947-4-1 | ||||||
Product Certifications | UL, CCC, TÜV | ||||||
Permissible Ambient Air Temperature Around the Device | -40 °C…70 °C (-40 °F…158 °F) for normal operating -40 °C…70 °C (-40 °F…158 °F) for storage | ||||||
Height | 95 mm | ||||||
Width | 60.2 mm | ||||||
Depth | 75 mm | ||||||
Net Weight | 0.44 kg | ||||||
Packing Units | |||||||
Unit Type of Package (bulk package) | 1 carton | ||||||
Number of Units in Package | 30 pcs | ||||||
Package Height | 215 mm | ||||||
Package Width | 340 mm | ||||||
Package Length | 360 mm | ||||||
Package Weight | 14.2 kg | ||||||
Offer Sustainability | |||||||
REACH Regulation | Conforming | ||||||
EU RoHS Directive | Conforming | ||||||
Mercury Free | Yes | ||||||
China RoHS Regulation | Conforming | ||||||
RoHS Exemption Information | Yes | ||||||
Contractual Warranty | |||||||
Warranty | 18 months |
Dimensions
XMC0 3P 25-40A(3NO)
AC Contactor: